SIMATIC DP, 5 ELECTRON. MODULES FOR ET 200S, 2 DI HIGH FEATURE 24V DC, 15 MM WIDTH WITH PARAM. F. INPUT DELAY DIAGNOSIS F. ENCODER SHORT- CIRCUIT W. LED SF (GROUP FAULT) 5 PIECES PER PACKAGING UNIT |
| Supply voltage |
| 24 V DC |
Yes; From power module |
| permissible range, lower limit (DC) |
20.4 V |
| permissible range, upper limit (DC) |
28.8 V |
| Reverse polarity protection |
Yes |
| Input current |
| from backplane bus 3.3 V DC, max. |
10 mA |
| from supply voltage L+, max. |
Dependent on encoder |
| Encoder supply |
| Output voltage |
min. L+ (-0.5 V), under load |
| Short-circuit protection |
Yes; Electronic |
| Output current |
| ● Output current, rated value |
500 mA |
| ● Output current, permissible range |
0 to 500 mA |
| Power loss |
| Power loss, typ. |
0.4 W |
| Address area |
| Address space per module |
| ● with packing |
2 bit |
| ● without packing |
1 byte |
| Digital inputs |
| Number of digital inputs |
2 |
| Input characteristic curve in accordance with IEC 61131, type 1 |
Yes |
| Input voltage |
| ● Type of input voltage |
DC |
| ● Rated value, DC |
24 V |
| ● for signal "0" |
-30 to +5 V |
| Input current |
| ● for signal "1", typ. |
8 mA |
| Input delay (for rated value of input voltage) |
| for standard inputs |
| — parameterizable |
Yes; 0.1 / 0.5 / 3 / 15 ms |
| — at "0" to "1", min. |
0.05 / 0.4 / 2.7 / 14.85 |
| — at "0" to "1", max. |
0,15 / 0,6 / 3,3 / 15,15 |
| — at "1" to "0", min. |
0.05 / 0.4 / 2.7 / 14.85 |
| — at "1" to "0", max. |
0,15 / 0,6 / 3,3 / 15,15 |
| Cable length |
| ● Cable length, shielded, max. |
1 000 m |
| ● Cable length unshielded, max. |
600 m |
| Encoder |
| Connectable encoders |
| ● 2-wire sensor |
Yes |
| — permissible quiescent current (2-wire sensor), max. |
1.5 mA |
| Interrupts/diagnostics/status information |
| Diagnostic messages |
| ● Diagnostic functions |
Yes |
| ● Short-circuit |
Yes; Short-circuit of outputs to ground; module by module |
| Diagnostics indication LED |
| ● Group error SF (red) |
Yes |
| ● Status indicator digital input (green) |
Yes; per channel |
| Parameter |
| Remark |
3 byte |
| Diagnostics short-circuit |
Disable / enable |
| Galvanic isolation |
| Galvanic isolation digital inputs |
| ● between the channels |
No |
| ● between the channels and the backplane bus |
Yes |
| Permissible potential difference |
| between different circuits |
75 VDC / 60 VAC |
| Isolation |
| Isolation tested with |
500 V DC |
| Dimensions |
| Width |
15 mm |
| Height |
81 mm |
| Depth |
52 mm |
| Weights |
| Weight, approx. |
35 g |
| last modified: |
21.08.2014 |