SIMATIC DP, 5 ELECTRON. MODULES FOR ET 200S, 4 DO HIGH FEATURE DC 24V/0.5A, 15 MM WIDTH DIAGNOSIS SHORT CIRCUIT, SF-LED 5 PIECES PER PACKAGING UNIT |
|
| Supply voltage |
| Reverse voltage protection |
Yes; when using the same load voltage as on the power module |
| Load voltage L+ |
| Rated value (DC) |
24 V; From power module |
| Reverse polarity protection |
Yes; polarity reversal can lead to the digital outputs being connected through |
| Input current |
| from load voltage L+ (without load), max. |
5 mA; Per channel |
| from backplane bus 3.3 V DC, max. |
10 mA |
| Address area |
| Address space per module |
| with packing |
4 bit |
| without packing |
1 byte |
| Digital outputs |
| Number of digital outputs |
4 |
| Short-circuit protection |
Yes |
| Response threshold, typ. |
0.7 to 1.5 A |
| Limitation of inductive shutdown voltage to |
-55 to -60 V, L+( ) |
| Controlling a digital input |
Yes |
| Switching capacity of the outputs |
| Lamp load, max. |
5 W |
| Load resistance range |
| lower limit |
48 Ω |
| upper limit |
3400 Ω |
| Output voltage |
| for signal "1", min. |
L+ (-1 V) |
| Output current |
| for signal "1" rated value |
0.5 A |
| for signal "1" permissible range for 0 to 60 °C, min. |
7 mA |
| for signal "1" permissible range for 0 to 60 °C, max. |
600 mA |
| for signal "0" residual current, max. |
0.3 mA |
| Output delay with resistive load |
| "0" to "1", max. |
100 µs |
| "1" to "0", max. |
300 µs |
| Parallel switching of 2 outputs |
| for uprating |
No |
| for redundant control of a load |
Yes; per module |
| Switching frequency |
| with resistive load, max. |
100 Hz |
| with inductive load, max. |
2 Hz |
| on lamp load, max. |
10 Hz |
| Total current of the outputs (per group) |
| all mounting positions |
| up to 60 °C, max. |
2 A |
| Cable length |
| Cable length, shielded, max. |
1000 m |
| Cable length unshielded, max. |
600 m |
| Isochronous mode |
| Isochronous mode (application synchronized up to terminal) |
Yes |
| Interrupts/diagnostics/status information |
| Diagnostic messages |
| Diagnostic functions |
Yes |
| Short-circuit |
Yes; Module-wise |
| Diagnostics indication LED |
| Group error SF (red) |
Yes; SF-LED (red) |
| Status indicator digital output (green) |
Yes; Per channel |
| Galvanic isolation |
| Galvanic isolation digital outputs |
| between the channels |
No |
| between the channels and the backplane bus |
Yes |
| Isolation |
| Isolation tested with |
500 V DC |
| Dimensions |
| Width |
15 mm |
| Height |
81 mm |
| Depth |
52 mm |
| Weights |
| Weight, approx. |
40 g |
| Status |
Jul 14, 2014 |