SIMATIC DP, 1 ELECTRON. MODULE FOR ET 200S, 8 DO DC24V/0,5A, 15 MM WIDTH, 1 PIECE PER PACKAGING UNIT |
| Supply voltage |
| Reverse voltage protection |
Yes |
| Load voltage L+ |
| ● Rated value (DC) |
24 V |
| ● Reverse polarity protection |
Yes |
| Input current |
| from load voltage L+ (without load), max. |
5 mA; Per channel |
| from backplane bus 3.3 V DC, max. |
10 mA |
| Power losses |
| Power loss, typ. |
1.5 W |
| Address area |
| Address space per module |
| ● without packing |
1 byte |
| Digital outputs |
| Number of digital outputs |
8 |
| short-circuit protection |
Yes |
| ● Response threshold, typ. |
o.k. |
| Limitation of inductive shutdown voltage to |
o.k. |
| Controlling a digital input |
Yes |
| Switching capacity of the outputs |
| ● Lamp load, max. |
5 W |
| Load resistance range |
| ● lower limit |
48 Ω |
| ● upper limit |
3 400 Ω |
| Output voltage |
| ● for signal "1", min. |
o.k. |
| Output current |
| ● for signal "1" rated value |
0.5 A |
| ● for signal "1" permissible range for 0 to 60 °C, min. |
7 mA |
| ● for signal "1" permissible range for 0 to 60 °C, max. |
600 mA |
| ● for signal "0" residual current, max. |
0.3 mA |
| Output delay with resistive load |
| ● "0" to "1", max. |
300 µs |
| ● "1" to "0", max. |
600 µs |
| Parallel switching of 2 outputs |
| ● for increased power |
No |
| ● for redundant control of a load |
Yes |
| Switching frequency |
| ● with resistive load, max. |
100 Hz |
| ● with inductive load, max. |
2 Hz |
| ● on lamp load, max. |
10 Hz |
| Aggregate current of outputs (per group) |
| all mounting positions |
| — up to 60 °C, max. |
4 A |
| Cable length |
| ● Cable length, shielded, max. |
1 000 m |
| ● Cable length unshielded, max. |
600 m |
| Isochronous mode |
| Isochronous operation (application synchronized up to terminal) |
Yes; jitter incumbered < 100us |
| Interrupts/diagnostics/status information |
| Diagnostic messages |
| ● Diagnostic functions |
No |
| Diagnostics indication LED |
| ● Status indicator digital output (green) |
Yes |
| Parameter |
| Remark |
3-byte parameter (not accessible for the user) |
| Galvanic isolation |
| Galvanic isolation digital outputs |
| ● between the channels |
No |
| ● between the channels and the backplane bus |
Yes |
| Isolation |
| Isolation checked with |
500 V DC |
| Dimensions |
| Width |
15 mm |
| Height |
81 mm |
| Depth |
52 mm |
| Weights |
| Weight, approx. |
40 g |
| last modified: |