SIMATIC DP, 5 ELECTRON. MODULES FOR ET 200S, 2 DO 24...230V AC, 15 MM WIDTH 5 PIECES PER PACKAGING UNIT |
|
| Supply voltage |
| Reverse voltage protection |
Yes; when using the same load voltage as on the power module |
| Load voltage L1 |
| permissible range, lower limit (AC) |
24 V; From power module |
| permissible range, upper limit (AC) |
230 V |
| Input current |
| from load voltage L+ (without load), max. |
30 mA |
| from backplane bus 3.3 V DC, max. |
18 mA |
| Power loss |
| Power loss, typ. |
4 W |
| Address area |
| Address space per module |
| with packing |
2 bit |
| without packing |
1 byte |
| Digital outputs |
| Number of digital outputs |
2 |
| Short-circuit protection |
Yes |
| Limitation of inductive shutdown voltage to |
-55 to -60 V |
| Controlling a digital input |
Yes; possible |
| Switching capacity of the outputs |
| Lamp load, max. |
100 W |
| Output voltage |
| for signal "1", min. |
L+ (-1.5 V) |
| Output current |
| for signal "1" rated value |
2 A |
| for signal "1" permissible range for 0 to 60 °C, min. |
0.1 mA |
| for signal "1" permissible range for 0 to 60 °C, max. |
2.2 A |
| for signal "0" residual current, max. |
3 mA |
| Output delay with resistive load |
| "0" to "1", max. |
15 ms |
| "1" to "0", max. |
15 ms |
| Parallel switching of 2 outputs |
| for uprating |
No |
| for redundant control of a load |
Yes; per module |
| Switching frequency |
| with resistive load, max. |
10 Hz |
| with inductive load, max. |
0.5 Hz |
| on lamp load, max. |
1 Hz |
| Total current of the outputs (per group) |
| all mounting positions |
| up to 40 °C, max. |
2 A |
| up to 50 °C, max. |
1.5 A |
| up to 60 °C, max. |
1 A |
| Cable length |
| Cable length, shielded, max. |
1000 m |
| Cable length unshielded, max. |
600 m |
| Interrupts/diagnostics/status information |
| Diagnostic messages |
| Diagnostic functions |
No |
| Diagnostics indication LED |
| Status indicator digital output (green) |
Yes |
| Parameter |
| Remark |
3 byte |
| Behavior on CPU/master STOP, channel-wise |
Substitute a value/keep last value, 0/1 |
| Galvanic isolation |
| Galvanic isolation digital outputs |
| between the channels |
No |
| between the channels and the backplane bus |
Yes |
| Isolation |
| Isolation tested with |
2500 V DC |
| Dimensions |
| Width |
15 mm |
| Height |
81 mm |
| Depth |
52 mm |
| Weights |
| Weight, approx. |
37 g |
| Status |
Jul 7, 2014 |